72 to 110 KvA 50 Hz Diesel Generator

SKU: GTB72 Category:

Description

Logo

Engine

  • Baudouin heavy duty diesel engine
  • 4-cycle, water cooled, turbo charged, direct injection
  • 12 Volt starter motor and charge alternator with battery, rack and cables
  • Replaceable air, fuel and oil filter
  • Industrial type radiator
  • Flexible fuel piping
  • Oil sump drain valve and extension pipe
  • Industrial/Residential type exhaust silencer
  • Maintenance free battery
  • Jacket Water Heater
  • Diesel gen-set maintenance and operating instructions and electrical circuit diagram

Alternator

  • Brushless, single bearing,4-pole alternator coupled with flexible disc coupling H type insulation class

Controls

  • IP 23 protection
  • Self exciting
  • Electronic AVR
  • Control panel Datakom Smart Series mains sensing or remote start control module
  • Emergency stop push button
  • Output circuit breaker
  • Static battery charger
  • Ready for remote monitoring

Housing

  • Modular type sound-proof canopy
  • Built from galvanized steel and epoxy, polyester powder painted
  • Lockable doors on both sides of canopy designed for easy access to essential replacement parts
  • Emergency stop push button
  • Control Panel viewing window
  • Bunded base fuel tank (Optional)
  • Forklift Pockets
  • Power cable entry with a gland plate

Standby Power

  • Applicable for supplying power to varying electrical load for the duration of power interruption
    of a reliable utility source, Overload is not allowed.

Prime Power

  • Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source, Overload is not allowed.
  • The maximum power which a generating set is capable of delivering continuously whilst                                                                                                                                                        supplying a variable electrical load.
  • Average load should be 70%.
  • The generator can be overloaded 10% for 1 hour per 12 hrs.

Base Power

  • Continuous power rating is used in applications where supplying power is at a constant 100% load for an unlimited number of hours each year.

Control Module

  • Datakom Smart 500 Control Module
  • State of the art, microprocessor controlled 4line, 64 x 132 pixel display LCD display
  • Automatic mains failure sensing
  • Front panel manual programming
  • User friendly setup and button layout
  • Remote start
  • Event logging, showing date and time
  • Stop/Reset, Manual
Displays
  • Engine Speed (rpm)
  • Oil pressure
  • Fuel Level (%)
  • Coolant temperature
  • Running Hours
  • Battery voltage monitoring
  • Generator Voltage (LL, LN)
  • Generator Current (L1-L2-L3)
  • Generator Frequency (Hz)
  • Generator Load & Power Monitoring (kW, kVA, kVAr, pf)
  • Mains Voltage (LL, LN)
  • Mains Frequency
  • Generator Set Ready
  • Mains Ready

Alarms

  • High coolant temperature
  • Low Fuel Level
  • Low oil pressure
  • Charge failure
  • Battery Low/High voltage
  • Fail to start
  • Fail to stop
  • High/Low Generator voltage
  • Generator Over/Under frequency
  • Generator Over/Under Speed

Technical Specification

      GTB77              GT88 GTB110
Output  Standby KvA 72 88 110
Kw 58 70 88
Prime KvA 65 80 100
Kw 52 64 80
Engine Engine Baudoin Baudoin Baudoin
  Model 54M11G70/5e2 4M11G90/5e2 4M11G70/5e2
  Configuration Inline Inline Inline
  Number of cylinders 4 4 4
  Speed RPM 1500 1500 1500
  Displacement Litres 4.5 4.5 4.5
  Bore / Stroke mm 105×130 105×130 105×130
  Compression 15.3 to 1 15.3 to 1 20.8 to 1
  Aspiration Turbo Charged Turbo Charged Turbo Charged
  Governor type Mech/Electronic Mech/Electronic Electronic
  Cooling Water type Water type Water type
  Cooling capacity Litres 15.3 15.3 20.8
  10 10 10
  Fuel Consumption 100% Load Litres / hr 14.5 17.8 23.3
  Fuel Consumption 75% Load Litres / hr 11 13.3 17.4
  Fuel Consumption 50% Load Litres / hr 7.7 9.2 11.9
Alternator Poles 3 3 3
  Phase 3 3 3
  Pole 4 4 4
  No of Leads 12 12 12
  Excitation AVR AVR AVR
  Insulation class H H H
  IP Protection IP23 IP23 IP23
  Power factor 0.8 0.8 0.8
  Frequency (Hz) 50 50 50
  Voltage 400 400 400
Size Canopy Set Dimensions (LxWxH) mm 2880x1000x1615 2880x1000x1615 3180 x 1050 x 1870
  Weight kg 1270 1355 1380
96  Open Set Dimensions mm 2400x1000x1520 2400x1000x1520 2700X1050x1850
  kg 1050 1135 1160
  Fuel Tank Capacity Litres 180 180 280

Additional information

Weight 1270 kg
Dimensions 2880 × 1000 × 1615 cm