Logo

Engine

  • YANGDONG heavy duty diesel engine
  • 4-cycle, water cooled, naturally aspirated, direct injection
  • 12 Volt starter motor and charge alternator with battery, rack and cables
  • Replaceable air, fuel and oil filter
  • Industrial type radiator
  • Flexible fuel piping
  • Oil sump drain valve and extension pipe
  • Industrial/Residential type exhaust silencer
  • Maintenance free battery
  • Jacket Water Heater
  • YANGDONG heavy duty diesel engine
  • Diesel gen-set maintenance and operating instructions and electrical circuit diagram

Alternator

  • Brushless, single bearing,4-pole alternator coupled with flexible disc coupling H type insulation class

Controls

  • IP 23 protection
  • Self exciting
  • Electronic AVR
  • Control panel Datakom Smart 500 mains sensing or remote start control module
  • Emergency stop push button
  • Output circuit breaker
  • Static battery charger
  • Ready for remote monitoring

Housing

  • Modular type sound-proof canopy
  • Built from galvanized steel and epoxy, polyester powder painted
  • Lockable doors on both sides of canopy designed for easy access to essential replacement parts
  • Emergency stop push button
  • Control Panel viewing window
  • Bunded base fuel tank (Optional)
  • Forklift Pockets
  • Power cable entry with a gland plate

Standby Power

  • Applicable for supplying power to varying electrical load for the duration of power interruption
    of a reliable utility source, Overload is not allowed.

Prime Power

  • Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source, Overload is not allowed.
  • The maximum power which a generating set is capable of delivering continuously whilst                                                                                                                                                        supplying a variable electrical load.
  • Average load should be 70%.
  • The generator can be overloaded 10% for 1 hour per 12 hrs.

Base Power

  • Continuous power rating is used in applications where supplying power is at a constant 100% load for an unlimited number of hours each year.

Control Module

  • Datakom Smart 500 Control Module
  • State of the art, microprocessor controlled 4line, 64 x 132 pixel display LCD display
  • Automatic mains failure sensing
  • Front panel manual programming
  • User friendly setup and button layout
  • Remote start
  • Event logging, showing date and time
  • Stop/Reset, Manual
  • Displays
  • Engine Speed (rpm)
  • Oil pressure
  • Fuel Level (%)
  • Coolant temperature
  • Running Hours
  • Battery voltage monitoring
  • Generator Voltage (LL, LN)
  • Generator Current (L1-L2-L3)
  • Generator Frequency (Hz)
  • Generator Load & Power Monitoring (kW, kVA, kVAr, pf)
  • Mains Voltage (LL, LN)
  • Mains Frequency
  • Generator Set Ready
  • Mains Ready

Alarms

  • High coolant temperature
  • Low Fuel Level
  • Low oil pressure
  • Charge failure
  • Battery Low/High voltage
  • Fail to start
  • Fail to stop
  • High/Low Generator voltage
  • Generator Over/Under frequency
  • Generator Over/Under Speed
  • Shut Downs
  • Fail to start
  • Emergency stop
  • Low oil pressure
  • High coolant temperature
  • Generator Over/Under frequency
  • Generator Over/Under Speed
  • High/Low Generator voltage
  • Oil pressure sensor open
  • Coolant temperature sensor open

Technical Specification

      GTY18ECM       
Output  Standby KvA 22
Kw 17.8
Prime KvA 20
Kw 16
Engine Engine YANGDONG
  Model YND485D
  Configuration Inline
  Number of cylinders 4
  Speed RPM 1500
  Displacement Litres 2.16
  Bore / Stroke mm 85×95
  Compression 18 to 1
  Aspiration Natural
  Governor type Mechanical
  Cooling Water type
  Cooling capacity Litres 12.5
  Fuel Consumption 100% Load Litres / hr 5
  Fuel Consumption 75% Load Litres / hr 4
  Fuel Consumption 50% Load Litres / hr 3
Alternator Poles 3
  Phase 3
  Pole 4
  No of Leads 12
  Excitation AVR
  Insulation class H
  IP Protection IP23
  Power factor 0.8
  Frequency (Hz) 50
  Voltage 400
Size Canopy Set Dimensions (LxWxH) mm 1900x900x1220
  Weight kg 694
  Open Set Dimensions mm 1600x900x1220
  kg 540
  Fuel Tank Capacity Litres 82